Why Your Aluminium Windows Sweat in Winter (And Why New Glass Rarely Fixes It)
Why Your Aluminium Windows Sweat in Winter (And Why New Glass Rarely Fixes It)
Every winter, the same email lands in our inbox: "Your windows are leaking. There's water all over the inside."
Nine times out of ten, the windows are not leaking. The water was never outside. It came out of the air in the room — and the window was simply the coldest thing it could find.
That distinction matters, because it decides whether you spend $400 on a dehumidifier or $40,000 on new glazing that solves nothing.
The one number that explains everything: dew point
Air holds water vapour. Warm air holds more of it than cold air. When air cools to a certain temperature, it can no longer hold what it's carrying and the excess condenses out as liquid. That temperature is the dew point.
A typical heated home in winter sits around 21°C and 55% relative humidity. The dew point of that air is roughly 11.5°C.
So any surface in your house below about 11.5°C will collect water. Not because it's defective — because it's cold.
On a 5°C night:
|
Surface |
Typical temperature |
What happens |
|
Single-glazed glass, centre |
4–6°C |
Heavy running condensation |
|
Aluminium frame, no thermal break |
8–10°C |
Water on frame faces, corners and sill |
|
Thermally broken frame + double glazing |
15–17°C |
Stays dry at normal humidity |
|
Double glazing, outer pane (outside face) |
2–4°C |
Dew on the outside — this is normal |
That last row surprises people every year. Dew on the outside of a new double-glazed unit is not a fault. It means the outer pane is now insulated from your heated room, so it runs cold, so outdoor humidity condenses on it. It's evidence the unit is doing its job.
Where the water appears tells you what to fix
Before you call anyone, look at where the moisture is. The location is a diagnosis.
Water along the bottom of the glass, only on the first cold snap, gone by mid-morning. Normal. The glass edge is the coldest part of the pane. Improve ventilation and it stops.
Water on the frame faces and in the corners, while the glass stays mostly clear. Classic cold bridge. The frame is conducting outdoor cold straight to the warm side. This is the single most common failure of cheap aluminium windows, and no amount of glass upgrading will fix it.
Water or fog between the two panes. That's a failed perimeter seal on the insulated glass unit (IGU). Moisture has entered the cavity. It's a warranty item, and the unit has to be replaced. This is the only case on this list where the window genuinely is broken.
Water at the top of the glass, or on the ceiling corner above the window. Look elsewhere. Rising damp, a roof or flashing leak, or a wall with no cavity. The window is a witness, not the culprit.
Black mould spots in the reveal or on the sill, with no visible water. Chronic low-level condensation that you've been wiping away for years. The mould is the receipt.
Why "just put in double glazing" often disappoints
A window is not a sheet of glass. It's a frame, a spacer, two seals and a pane — and heat takes the easiest path out, which is rarely the glass.
Aluminium is a superb conductor: around 160–200 W/m·K. Polyamide — the material used for a proper thermal break — is about 0.3 W/m·K. Fitting a 20–24 mm polyamide strip between the outer and inner profiles is not a marketing flourish; it's what stops the frame from acting as a radiator fin that runs cold on the inside.
Two more details get skipped when someone quotes you a "double glazed aluminium window":
- The spacer bar. Standard aluminium box spacers conduct cold around the entire perimeter of the unit, which is why the edge of the glass is always the first place to fog. Warm-edge spacers (thermally broken or structural foam) keep that edge closer to room temperature.
- The gaskets and drainage. A frame with EPDM gaskets and a proper baffled drainage path keeps the inner chamber dry. A frame with hard PVC seals and one drilled hole will let water track inward under wind pressure.
So the order of effectiveness is:
- Ventilate. Extract fans ducted to the outside (not recirculating), lids on pots, clothes dried in a vented dryer or outside. Dropping indoor humidity from 65% to 50% moves the dew point by about 4°C, which is often the whole problem.
- Break the thermal bridge. Thermally broken profiles, warm-edge spacers.
- Then upgrade the glass. Low-E, argon, wider cavity.
- Never seal a wet room airtight and hope. Moisture has to leave somewhere, and it will choose your plaster.
Three things not to do
- Don't tape over the weep holes. They are the drainage path. Blocking them turns a minor weep into a wall cavity full of water.
- Don't wipe and forget. If water sits on a powder-coated sill or in a timber reveal, the finish and the lining fail long before the window does.
- Don't replace perfectly good glass to fix a ventilation problem. Start with a $15 hygrometer. If your indoor humidity is over 60%, you have your answer.
The short version
Condensation is not a defect in the window; it's an argument between humidity and temperature, and the window is where the argument happens. Fix the humidity, break the thermal bridge, and keep the glass as the third step, not the first.
If you're not sure which of those you're looking at, send us a photo of the frame and the sill on a cold morning, plus your rough indoor humidity. We'll tell you which one it is — even if the answer is "your windows are fine, buy a fan."
FAQ
Why does my new double glazing have water on the outside? Because the outer pane is now insulated from the warm room and sits close to the outdoor dew point. It's normal, it's seasonal, and it's a sign the unit is insulating. Water on the inside of the inner pane is the thing to investigate.
Will triple glazing stop condensation? It reduces it, because the inner surface runs warmer. But if indoor humidity stays above 65%, you'll still get water — on the glass, or worse, on the wall. Deal with moisture first.
Is condensation covered by warranty? Surface condensation is a building physics outcome, not a manufacturing fault, so it isn't. Moisture inside the sealed cavity is a failed unit and is normally covered.